ABB i-bus
KNX
Commissioning
Send status via object "Activate
fct Staircase lighting/Status"
Options:
Linked group object:
No: The status of the Activate staircase lighting function is not transmitted on the KNX.
Yes: The Activate fct Staircase lighting/Status group object does not just activate or deactivate the
Staircase lighting function. It also transmits the activation status on the KNX.
No
Yes
Selection of Yes option:
Dependent parameters:
Send object value
Options:
On change
On request
After a change or on request
On change: The status is sent when a change occurs.
On request: The status is sent when a request occurs.
After a change or on request: The status is sent when either a change or request occurs.
Activate fct Staircase lighting/Status