Commissioning
Enable Group object
"Status switch"
Options:
Linked group object:
Yes: The (DALI output X) Status switch group object is enabled. It sends a 1-bit telegram on the KNX,
signaling the current switch status.
No: The status of the switch state is not actively sent on the KNX.
54 2CDC507164D0201 | DG/S x.64.1.1
Yes
No
Selection of Yes option:
Dependent parameters:
Send object value
Options:
On change
On request
After a change or on request
On change: The status is sent when a change occurs.
On request: The status is sent when a request occurs.
After a change or on request: The status is sent when either a change or request occurs.
Value for different switching
states at DALI output
Options:
ON
OFF
This parameter defines the status to be sent if DALI devices with different states are present on the
output.
ON: The switch status is sent as ON (telegram value 1) if at least one DALI device is
switched on.
OFF: The switch status is only sent as ON (telegram value 1) if all DALI devices are
switched on.