ABB i-bus KNX Product Manual page 32

Dali-gateway basic dg/s x.64.1.1
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Commissioning
Enable manual operation.
Obj "Disable manual operation/Status"
Options:
Linked group object:
This parameter disables or enables the
If manual operation is enabled, it can be disabled or enabled by the Disable manual operation/Status
group object. Its disabled status is also displayed.
Yes: Manual
mode, all DALI devices can be switched on and off to check the cable connections and verify that they
are correct. Pressing the button for more than 5 seconds triggers DALI addressing which assigns a
DALI address to any DALI devices without one.
No: The
Brightness value on exiting
manual operation
Options:
These parameters define the brightness value of DALI devices on the output on exiting manual operation.
Manual brightness setting retained: the last brightness value set during manual operation is retained
on exiting manual operation.
Refreshed KNX state: The brightness value set before manual operation is updated and set when
manual operation ends. Therefore KNX any incoming commands during manual operation are
updated in the background.
30 2CDC507164D0201 | DG/S x.64.1.1
Yes
No
Disable manual operation/Status
is enabled. Pressing the
push button is disabled. No manual action is possible on the device.
Manual brightness setting retained
Refreshed KNX state
push button on the front of the DG/S.
push button for 2-5 seconds activates test mode. In this

Advertisement