Mitsubishi Electric GOT2000 Series User Manual page 145

Graphic operation terminal
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

Error message
Failed to verify with PLC. Please
check the [drive name] drive.
Parameter file is corrupted.
Please restart the ladder editor.
■2. Error messages for communication
Error message
Failed to communicate with CPU.
Failed to communicate with CPU.
Failed to get the information of
CPU because of bad connection.
Failed to get the information.
The CPU protect switch is ON.
Turn OFF the protect switch.
The CPU is not in STOP mode.
Please change the CPU to STOP
mode.
CPU drive error. Please confirm
the drive status.
The specified file does not exist in
the CPU. Please confirm the file in
the drive.
The specified file in the CPU is
invalid. Please confirm the file in
the drive.
The file cannot be accessed while
it is being accessed by other
connected equipment or it is being
transferred.
Description
The GOT cannot access the
temporary file in the data storage
during the PLC program verification.
The parameter file in the data storage
is corrupted.
Description
The GOT cannot communicate with
the PLC CPU.
The GOT cannot communicate with
the PLC CPU.
The GOT cannot communicate with
the PLC CPU.
• The GOT cannot communicate
with the PLC CPU.
• A file with faulty file name is
selected.
• The system protect switch of the
PLC CPU is on.
• The PLC CPU is in the boot
process.
Any operation that the PLC CPU
cannot execute during running is
performed.
The target drive does not function.
The specified file does not exist in the
PLC CPU.
The specified file in the PLC CPU is
corrupted.
• Other GOTs or GX Works2/GX
Developer access the connected
PLC CPU.
• The QCPU transfers program files
from the program cache memory to
the program memory.
4.10 Error Messages and Corrective Action
Corrective action
• Insert a data storage without a format error in the
GOT.
• Close the SD card cover.
• Delete files in the data storage.
• Insert a data storage with a large capacity.
• Cancel the write-protect setting for the folder that
is used for the sequence program monitor (ladder)
in the data storage.
Exit the sequence program monitor (ladder), and
then start the function again.
Corrective action
• Check the line status between the GOT and the
PLC CPU, and make the GOT communicate with
the PLC CPU.
• Check if the PLC CPU supports the sequence
program monitor (ladder).
• Check the line status between the GOT and the
PLC CPU, and make the GOT communicate with
the PLC CPU.
• Check if the PLC CPU supports the sequence
program monitor (ladder).
Check the line status between the GOT and the PLC
CPU, and make the GOT communicate with the PLC
CPU.
• Check the communications between the GOT and
PLC CPU, and make sure that the GOT
communicates with the PLC CPU.
• Select the file after changing the message display
language to one which can display the file name in
the utility.
• Change the file name with GX Works2/GX
Developer.
• Turn off the system protect switch of the PLC CPU.
• Wait until the boot process of the PLC CPU is
completed.
Set the PLC CPU to the STOP status.
Format the target drive by using GX Works2/GX
Developer.
Check files in the specified drive of the PLC CPU.
Delete the specified file by using GX Works2/GX
Developer, and then create the file again.
• Access the file when other devices do not access
the connected PLC CPU.
• Access the file after QCPU completes the
transference from the program cache memory to
the program memory.