■5. Online module change
To enable the online module change, configure the setting in [System Launcher] of [Ext. func. set] in the utility.
Set [Online module change] to [Effective].
GOT2000 Series User's Manual (Utility)
2.2.2

Precautions

■1. Display of the system configuration diagram
The system configuration diagram has two types: the system configuration diagram for the system launcher and the
one for the extended function.
When you select a module supported by the system launcher, the system configuration diagram for the system
launcher appears.
When you select a module unsupported by the system launcher, the system configuration diagram for the extended
function used appears if it is available.
For the screen transition of the system configuration diagram for the extended function, refer to the extended function
used.
When the system application (extended function) for the system launcher is not installed on the GOT, even though you
select a module supported by the system launcher, the system configuration diagram for the extended function used
appears.
■2. Precautions for online module change
When you replace a module of a PLC while the PLC is on line, the target module stops its operation.
Check that the operations of the PLC are not affected, and then replace the module.
The following shows the applicable modules.
• QCPU(Q mode)
Input module, Output module, Input/Output module, Analog input module, Analog output module, Temperature input
module, Temperature control module, Loop control module, Pulse input module
For the details of the online module change, refer to the following.
Manual of the CPU or module used
2.2 Specifications