■2. Setting display mode of SFC programs
The display mode of SFC programs on the SFC diagram monitor screen can be set.
The MELSAP-L program display mode is available regardless of the read SFC program format (MELSAP3, MELSAP-
L).
In the MELSAP-L program display mode, operation output/transition condition sequence programs are displayed as
[?????] when the GOT displays a SFC program with the MELSAP3 format.
The following shows how the GOT displays sequence programs with and without the MELSAP-L program display
mode.
Item
Displayed operation output/transition
condition sequence program
■3. Setting zoom comment display mode
Whether to display or hide comments and notes in the zoom window can be set.
■4. Switching display formats between decimal and hexadecimal numbers
The display formats of word device values on the SFC diagram monitor screen can be switched between decimal and
hexadecimal numbers.
■5. Setting automatic scroll mode
The automatic scroll can be switched between enabled or disabled states.
In the automatic scroll mode, the GOT displays active steps on the SFC diagram monitor screen by automatically
scrolling the screen when all the following conditions are satisfied.
• No active step is displayed on the SFC diagram monitor screen.
• The displayed block has an active step.
For setting the automatic scroll mode, refer to the following.
For the SFC diagram monitor screen, refer to the following.
5 - 12
5.3 Operations for Display
5.6.3 ■2. [Display] menu
With MELSAP-L program display mode
The GOT displays a sequence program
on the SFC diagram monitor screen.
5.6.3 ■3. Monitoring Mode menu
5.6.3 ■2. [Display] menu
The step status becomes inactive.
5.6.3 ■2. [Display] menu
5.6 How to Operate SFC Diagram Monitor Screen
Without MELSAP-L program display
mode
The GOT displays a sequence program in
the zoom window by touching a step or
transition condition on the SFC diagram
monitor screen.
An active step in the block is
displayed by automatically
scrolling the screen.