Section 6
Differential protection
6.2.5
6.2.6
120
Signal
IN
IBIAS
IDIFF
ANGLE
I2RATIO
Settings
Table 33:
Basic general settings for the function REFPDIF (REF1-)
Parameter
Range
GlobalBaseSel
1 - 6
Table 34:
Basic parameter group settings for the function REFPDIF (REF1-)
Parameter
Range
Operation
Off
On
IdMin
4.0 - 100.0
Table 35:
Advanced parameter group settings for the function REFPDIF (REF1-)
Parameter
Range
ROA
60 - 90
Monitored data
Table 36:
REFPDIF (87N) Monitored data
Name
Type
IRES
REAL
IN
REAL
IBIAS
REAL
Table continues on next page
Description
Magnitude of fundamental frequency neutral current
Magnitude of the bias current
Magnitude of fundamental frequency differential current
Direction angle from zero sequence feature
Second harmonic ratio
Step
Default
1
1
Step
Default
-
Off
0.1
10.0
Step
Default
1
60
Values (Range)
Unit
-
A
-
A
-
A
1MRK 502 048-UUS A
Unit
Description
-
Selection of one of the
Global Base Value groups
Unit
Description
-
Operation Off / On
%IB
Maximum sensitivity in %
of IBase
Unit
Description
Deg
Relay operate angle for
zero sequence directional
feature
Description
Magnitude of fundamental
frequency residual current
Magnitude of fundamental
frequency neutral current
Magnitude of the bias current
Technical manual