Settings - ABB Relion Technical Manual

Generator protection
Hide thumbs Also See for Relion:
Table of Contents

Advertisement

1MRK 502 048-UUS A
8.8.5
Table 137:
AEGGAPC (50AE) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
I>
5 - 900
tOC
0.000 - 60.000
ArmU<
2 - 150
tArm
0.000 - 60.000
DisarmU>
2 - 200
tDisarm
0.000 - 60.000
Table 138:
AEGGAPC (50AE) Non group settings (basic)
Name
Values (Range)
GlobalBaseSel
1 - 6
8.8.6
8.8.7
Technical manual

Settings

Unit
Step
-
-
%IB
1
s
0.001
%VB
1
s
0.001
%VB
1
s
0.001
Unit
Step
-
1
Monitored data
Table 139:
AEGGAPC (50AE) Monitored data
Name
Type
IMAX
REAL
UMAX
REAL
Operation principle
Accidental energizing protection for synchronous generator AEGGAPC (50AE) function
is connected to three phase current input either from the generator terminal side or from
generator neutral point side and three phase voltage from the generator terminals. The
maximum of the three phase-to-phase voltages and maximum of the three phase currents
are measured.
When the maximum phase-to-phase voltage is less than the 27_pick_up for the period
tArm, it is ensured that the generator is off-line. The Enabled signal will initiate the arming
and enable the overcurrent function. If the calculated maximum current of the three phases
Default
Description
Disabled
Disable/Enable Operation
120
Phase current pickup in % of IBase
0.030
Trip time daly for overcurrent level
50
Undervoltage level to arm protection in % of
Vbase
5.000
Time delay to arm protection with undervoltage
pickup
80
Over voltage level to disarm protection in % of
Vbase
0.500
Time delay to disarm protection when voltage
greater than drop out level
Default
Description
1
Selection of one of the Global Base Value
Groups
Values (Range)
Unit
-
A
-
kV
Section 8
Current protection
Description
Maximum value of current
Maximum value of phase to
phase voltage
263