Signals - ABB Relion Technical Manual

Generator protection
Hide thumbs Also See for Relion:
Table of Contents

Advertisement

Section 10
Frequency protection
10.1.4
10.1.5
Table 186:
SAPTUF (81) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
PUFrequency
35.00 - 75.00
tDelay
0.000 - 60.000
tRestore
0.000 - 60.000
RestoreFreq
45.00 - 65.00
10.1.6
10.1.7
320

Signals

Table 184:
SAPTUF (81) Input signals
Name
Type
V3P
GROUP
SIGNAL
BLOCK
BOOLEAN
Table 185:
SAPTUF (81) Output signals
Name
Type
TRIP
BOOLEAN
PICKUP
BOOLEAN
RESTORE
BOOLEAN
BLKDMAGN
BOOLEAN
Settings
Unit
Step
-
-
Hz
0.01
s
0.001
s
0.001
Hz
0.01
Monitored data
Table 187:
SAPTUF (81) Monitored data
Name
Type
FREQ
REAL
Operation principle
The underfrequency protection (SAPTUF, 81) function is used to detect low power
system frequency. If the frequency remains below the set value for a time period greater
Default
Description
-
Three phase group signal for voltage inputs
0
Block of function
Description
Common trip signal
General pickup signal
Restore signal for load restoring purposes
Measurement blocked due to low voltage amplitude
Default
Description
Disabled
Disable/Enable Operation
48.80
Frequency set value
0.200
Operate time delay
0.000
Restore time delay
49.90
Restore frequency if frequency is above
frequency value
Values (Range)
Unit
-
Hz
1MRK 502 048-UUS A
Description
Measured frequency
Technical manual