Function Block - ABB Relion Technical Manual

Generator protection
Hide thumbs Also See for Relion:
Table of Contents

Advertisement

1MRK 502 048-UUS A
11.2.3
11.2.4
11.2.5
Table 206:
TCSSCBR Non group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
tDelay
0.020 - 300.000
11.2.6
Technical manual

Function block

GUID-6F85BD70-4D18-4A00-A410-313233025F3A V2 EN
Figure 161:
Function block
Signals
Table 204:
TCSSCBR Input signals
Name
Type
TCS_STATE
BOOLEAN
BLOCK
BOOLEAN
Table 205:
TCSSCBR Output signals
Name
Type
ALARM
BOOLEAN
Settings
Unit
Step
-
-
s
0.001
Operation principle
The function can be enabled and disabled with the Operation setting. The corresponding
parameter values are Enable and Disable.
The operation of trip circuit supervision can be described by using a module diagram. All
the modules in the diagram are explained in the next sections.
Secondary system supervision
Default
Description
0
Trip circuit fail indication from I/O-card
0
Block of function
Description
Trip circuit fault indication
Default
Description
Enabled
Operation Disabled/Enabled
3.000
Operate time delay
Section 11
343

Advertisement

Table of Contents
loading

This manual is also suitable for:

650 seriesReg650 ansi

Table of Contents