Advertisement

Section 10
Frequency protection
10.2.3
10.2.4
10.2.5
Table 191:
SAPTOF (81) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
PUFrequency
35.00 - 75.00
tDelay
0.000 - 60.000
10.2.6
324

Function block

SAPTOF (81)
V3P*
TRIP
BLOCK
BFI
BLKDMAGN
ANSI09000280-1-en.vsd
ANSI09000280 V1 EN
Figure 151:
SAPTOF (81) function block
Signals
Table 189:
SAPTOF (81) Input signals
Name
Type
V3P
GROUP
SIGNAL
BLOCK
BOOLEAN
Table 190:
SAPTOF (81) Output signals
Name
Type
TRIP
BOOLEAN
BFI
BOOLEAN
BLKDMAGN
BOOLEAN
Settings
Unit
Step
-
-
Hz
0.01
s
0.001
Monitored data
Table 192:
SAPTOF (81) Monitored data
Name
Type
FREQ
REAL
Default
Description
-
Three phase group signal for voltage inputs
0
Block of function
Description
Common trip signal
General pickup signal
Measurement blocked due to low amplitude
Default
Description
Disabled
Operation Disable / Enable
51.20
Frequency set value
0.200
Operate time delay
Values (Range)
Unit
-
Hz
1MRK 502 048-UUS A
Description
Measured frequency
Technical manual