Section 9
Voltage protection
9.2.8
9.3
9.3.1
9.3.2
294

Technical data

Table 165:
OV2PTOV (59) technical data
Function
Operate voltage, step 1
and 2
Reset ratio
Inverse time
characteristics for steps 1
and 2, see table
577
Definite time delay, step 1
Definite time delays, step
2
Minimum operate time,
Inverse characteristics
Operate time, pickup
function
Reset time, pickup
function
Critical impulse time
Impulse margin time
Two step residual overvoltage protection ROV2PTOV
(59N)
Identification
Function description
Two step residual overvoltage
protection
Functionality
Residual voltages may occur in the power system during ground faults.
Two step residual overvoltage protection ROV2PTOV (59N) function calculates the
residual voltage from the three-phase voltage input transformers or measures it from a
Range or value
VBase
(1-200)% of
>98%
-
(0.00 - 6000.00) s
(0.000-60.000) s
(0.000-60.000) s
30 ms typically at 0 to 2 x V
set
40 ms typically at 2 to 0 x V
set
10 ms typically at 0 to 2 x V
set
15 ms typically
IEC 61850
identification
ROV2PTOV
1MRK 502 048-UUS A
Accuracy
± 0.5% of V
at V < V
n
± 0.5% of V at V > V
-
See table
577
± 0.5% ± 25 ms
± 0.5% ± 25 ms
± 0.5% ± 25 ms
-
-
-
-
IEC 60617
ANSI/IEEE C37.2
identification
device number
59N
3U0>
IEC10000168 V1 EN
Technical manual