Section 12
Control
12.2.4
12.2.4.1
366

Circuit switch SXSWI

Signals
Table 220:
SXSWI Input signals
Name
Type
BLOCK
BOOLEAN
LR_SWI
BOOLEAN
OPEN
BOOLEAN
CLOSE
BOOLEAN
BL_OPEN
BOOLEAN
BL_CLOSE
BOOLEAN
BL_UPD
BOOLEAN
POSOPEN
BOOLEAN
POSCLOSE
BOOLEAN
TR_OPEN
BOOLEAN
TR_CLOSE
BOOLEAN
RS_CNT
BOOLEAN
XIN
BOOLEAN
Table 221:
SXSWI Output signals
Name
Type
XPOS
GROUP SIGNAL
EXE_OP
BOOLEAN
EXE_CL
BOOLEAN
OP_BLKD
BOOLEAN
CL_BLKD
BOOLEAN
UPD_BLKD
BOOLEAN
POSITION
INTEGER
OPENPOS
BOOLEAN
CLOSEPOS
BOOLEAN
TR_POS
INTEGER
CNT_VAL
INTEGER
L_CAUSE
INTEGER
Default
Description
0
Block of function
0
Local/Remote switch indication from switchyard
0
Pulsed signal used to immediately open the switch
0
Pulsed signal used to immediately close the switch
0
Signal to block the open command
0
Signal to block the close command
0
Steady signal for block of the position updating
0
Signal for open position of apparatus from I/O
0
Signal for close position of apparatus from I/O
0
Signal for open position of truck from I/O
0
Signal for close position of truck from I/O
0
Resets the operation counter
0
Execution information from CSWI
Description
Group connection to CSWI
Executes the command for open direction
Executes the command for close direction
Indication that the function is blocked for open
commands
Indication that the function is blocked for close
commands
Update of position indication is blocked
Apparatus position indication
Apparatus open position
Apparatus closed position
Truck position indication
Operation counter value
Latest value of the error indication during command
1MRK 502 048-UUS A
Technical manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

650 seriesReg650 ansi

Table of Contents