ABB Relion Technical Manual page 696

Generator protection
Hide thumbs Also See for Relion:
Table of Contents

Advertisement

Section 17
Basic IED functions
Table 514:
SMAI_20_1 Non group settings (advanced)
Name
Values (Range)
Negation
Disabled
NegateN
Negate3Ph
Negate3Ph+N
MinValFreqMeas
5 - 200
Table 515:
SMAI_20_12 Non group settings (basic)
Name
Values (Range)
GlobalBaseSel
1 - 6
DFTReference
InternalDFTRef
DFTRefGrp1
DFTRefGrp2
DFTRefGrp3
DFTRefGrp4
DFTRefGrp5
DFTRefGrp6
DFTRefGrp7
DFTRefGrp8
DFTRefGrp9
DFTRefGrp10
DFTRefGrp11
DFTRefGrp12
External DFT ref
ConnectionType
Ph-N
Ph-Ph
AnalogInputType
Voltage
Current
Table 516:
SMAI_20_12 Non group settings (advanced)
Name
Values (Range)
Negation
Disabled
NegateN
Negate3Ph
Negate3Ph+N
MinValFreqMeas
5 - 200
690
Unit
Step
Default
-
-
Disabled
%
1
10
Even if the AnalogInputType setting of a SMAI block is set to Current, the
MinValFreqMeas setting is still visible. This means that the minimum
level for current amplitude is based on VBase. For example, if VBase is
20000, the minimum amplitude for current is 20000 * 10% = 2000. This
has practical affect only if the current measuring SMAI is used as a
frequency reference for the adaptive DFT. This is not recommended, see
the Setting guidelines.
Unit
Step
Default
-
1
1
-
-
InternalDFTRef
-
-
Ph-N
-
-
Voltage
Unit
Step
Default
-
-
Disabled
%
1
10
1MRK 502 048-UUS A
Description
Negation
Limit for frequency calculation in % of VBase
Description
Selection of one of the Global Base Value
groups
DFT reference
Input connection type
Analog input signal type
Description
Negation
Limit for frequency calculation in % of VBase
Technical manual