Section 7
Impedance protection
7.5.2
7.5.3
7.5.4
7.5.5
Table 80:
LEPDIS Group settings (basic)
Name
Values (Range)
RLd
0.05 - 3000.00
LdAngle
5 - 85
188

Functionality

Heavy load transfer is common in many power networks and may make fault resistance
coverage difficult to achieve. In such a case, Load encroachment LEPDIS function can be
used to prevent operation of the of the underimpedance measuring zones during heavy
loads.
Each of the three measuring phase-to-phase loops has its own load encroachment
characteristic.
Function block
LEPDIS
I3P*
DLECND
V3P*
BLOCK
ANSI10000119-1-en.vsd
ANSI10000119 V1 EN
Figure 84:
LEPDIS function block
Signals
Table 78:
LEPDIS Input signals
Name
Type
I3P
GROUP
SIGNAL
V3P
GROUP
SIGNAL
BLOCK
BOOLEAN
Table 79:
LEPDIS Output signals
Name
Type
DLECND
INTEGER
Settings
Unit
Step
ohm/p
0.01
Deg
1
Default
Description
-
Three phase group signal for current inputs
-
Three phase group signal for voltage inputs
0
Block of function
Description
Binary coded starts from load encroachment
Default
Description
1.00
Load resistive reach in ohm/phase
38
Load encroachment inclination of load angular
sector