Function Block - ABB Relion Technical Manual

Generator protection
Hide thumbs Also See for Relion:
Table of Contents

Advertisement

1MRK 502 048-UUS A
9.3.3
9.3.4
Technical manual
single voltage input transformer fed from a broken delta or neutral point voltage
transformer.
ROV2PTOV (59N) has two voltage steps, where step 1 can be set as inverse or definite
time delayed. Step 2 is always definite time delayed.

Function block

ROV2PTOV (59N)
V3P*
TRIP
BLOCK
TRST1
BLK1
TRST2
BLK2
PICKUP
PU_ST1
PU_ST2
ANSI09000273_1_en.vsd
ANSI09000273 V1 EN
Figure 136:
ROV2PTOV (59N) function block
Signals
Table 166:
ROV2PTOV (59N) Input signals
Name
Type
V3P
GROUP
SIGNAL
BLOCK
BOOLEAN
BLK1
BOOLEAN
BLK2
BOOLEAN
Table 167:
ROV2PTOV (59N) Output signals
Name
Type
TRIP
BOOLEAN
TRST1
BOOLEAN
TRST2
BOOLEAN
PICKUP
BOOLEAN
PU_ST1
BOOLEAN
PU_ST2
BOOLEAN
Default
Description
-
Three phase group signal for voltage inputs
0
Block of function
0
Block of step 1
0
Block of step 2
Description
Common trip signal
Trip signal from step 1
Trip signal from step 2
General pickup signal
Start signal from step 1
Start signal from step 2
Section 9
Voltage protection
295

Advertisement

Table of Contents
loading

This manual is also suitable for:

650 seriesReg650 ansi

Table of Contents