Signals - ABB Relion Technical Manual

Generator protection
Hide thumbs Also See for Relion:
Table of Contents

Advertisement

Section 16
Station communication
16.6.4
16.6.5
Table 474:
GOOSEINTRCV Non group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
16.6.6
650

Signals

Table 472:
GOOSEINTRCV Input signals
Name
Type
BLOCK
BOOLEAN
Table 473:
GOOSEINTRCV Output signals
Name
Type
INTOUT
INTEGER
DATAVALID
BOOLEAN
COMMVALID
BOOLEAN
TEST
BOOLEAN
Settings
Unit
Step
-
-
Operation principle
The DATAVALID output will be HIGH if the incoming message is with valid data.
The COMMVALID output will become LOW when the sending IED is under total failure
condition and the GOOSE transmission from the sending IED does not happen.
The TEST output will go HIGH if the sending IED is in test mode.
The input of this GOOSE block must be linked in SMT by means of a cross
to receive the integer values.
The implementation for IEC61850 quality data handling is restricted to a
simple level. If quality data validity is GOOD then the DATAVALID
output will be HIGH. If quality data validity is INVALID,
QUESTIONABLE, OVERFLOW, FAILURE or OLD DATA then the
DATAVALID output will be LOW.
Default
Description
0
Block of function
Description
Integer output
Data valid for integer output
Communication valid for integer output
Test output
Default
Description
Disabled
Operation Off/On
1MRK 502 048-UUS A
Technical manual