Enclosure Class - ABB Relion Technical Manual

Generator protection
Hide thumbs Also See for Relion:
Table of Contents

Advertisement

1MRK 502 048-UUS A
19.8
Technical manual
Table 562:
IRIG-B
Type
Value
Input impedance
430 Ohm
Minimum input voltage
4.3 V
HIGH
Maximum input voltage
0.8 V
LOW
Table 563:
EIA-485 interface
Type
Value
Minimum differential
1.5 V
driver output voltage
Maximum output current
60 mA
Minimum differential
0.2 V
receiver input voltage
Supported bit rates
300, 600, 1200, 2400,
4800, 9600, 19200,
38400, 57600, 115200
Maximum number of 650
32
IEDs supported on the
same bus
Max. cable length
925 m (3000 ft)
Table 564:
Serial rear interface
Type
Serial port (X9)
Table 565:
Optical serial port (X9)
Wave length
Fibre type
820 nm
MM 62,5/125 µm
glass fibre core
820 nm
MM 50/125 µm
glass fibre core
1) Maximum allowed attenuation caused by fibre

Enclosure class

Accuracy
-
-
-
Conditions
-
-
-
-
Cable: AWG24 or better, stub lines shall be avoided
Counter connector
Optical serial port, type ST for IEC 60870-5-103 and
DNP serial
Connector
Permitted path attenuation
ST
6.8 dB (approx. 1700m length with 4 db /
km fibre attenuation)
ST
2.4 dB (approx. 600m length with 4 db / km
fibre attenuation)
Section 19
Technical data
1)
727