Name
Type
1189G_OP
BOOLEAN
1189G_CL
BOOLEAN
2189G_OP
BOOLEAN
2189G_CL
BOOLEAN
7189G_OP
BOOLEAN
7189G_CL
BOOLEAN
BB7_D_OP
BOOLEAN
BC_12_CL
BOOLEAN
BC_17_OP
BOOLEAN
BC_17_CL
BOOLEAN
BC_27_OP
BOOLEAN
BC_27_CL
BOOLEAN
VOLT_OFF
BOOLEAN
VOLT_ON
BOOLEAN
VP_BB7_D
BOOLEAN
VP_BC_12
BOOLEAN
VP_BC_17
BOOLEAN
VP_BC_27
BOOLEAN
EXDU_89G
BOOLEAN
EXDU_BPB
BOOLEAN
EXDU_BC
BOOLEAN
989_EX1
BOOLEAN
989_EX2
BOOLEAN
189_EX1
BOOLEAN
189_EX2
BOOLEAN
Table continues on next page
Default
Description
0
Grounding switch 1189G on busbar WA1 is in open
position
0
Grounding switch 1189G on busbar WA1 is in closed
position
0
Grounding switch 2189G on busbar WA2 is in open
position
0
Grounding switch 2189G on busbar WA2 is in closed
position
0
Grounding switch 7189G on busbar WA7 is in open
position
0
Grounding switch 7189G on busbar WA7 is in closed
position
0
Disconnectors on busbar WA7 except in the own bay
are open
0
A bus coupler connection exists between busbar WA1
and WA2
0
No bus coupler connection exists between busbar WA1
and WA7
0
A bus coupler connection exists between busbar WA1
and WA7
0
No bus coupler connection exists between busbar WA2
and WA7
0
A bus coupler connection exists between busbar WA2
and WA7
0
There is no voltage on the line and not VT (fuse) failure
0
There is voltage on the line or there is a VT (fuse) failure
0
Switch status of the disconnectors on busbar WA7 are
valid
0
Status of bus coupler apparatuses between bus1 and
bus 2 are valid.
0
Status of the bus coupler apparatuses between Bus1
and Bus7 are valid
0
Status of the bus coupler apparatus between Bus2 and
Bus7 are valid
0
No transmission error from any bay containing
grounding switches
0
No transmission error from any bay with disconnectors
on Bus7
0
No transmission error from any bus coupler bay
0
External condition for apparatus 989
0
External condition for apparatus 989
0
External condition for apparatus 189
0
External condition for apparatus 189
1MRK 502 048-UUS A