ABB Relion Technical Manual page 518

Generator protection
Hide thumbs Also See for Relion:
Table of Contents

Advertisement

Section 14
Monitoring
Name
Values (Range)
PDbRepInt
1 - 300
PZeroDb
0 - 100000
PHiLim
-2000.0 - 2000.0
PLowLim
-2000.0 - 2000.0
PLowLowLim
-2000.0 - 2000.0
PLimHyst
0.000 - 100.000
QDbRepInt
1 - 300
QZeroDb
0 - 100000
QHiHiLim
-2000.0 - 2000.0
QHiLim
-2000.0 - 2000.0
QLowLim
-2000.0 - 2000.0
QLowLowLim
-2000.0 - 2000.0
QLimHyst
0.000 - 100.000
UGenZeroDb
1 - 100
PFDbRepInt
1 - 300
PFZeroDb
0 - 100000
IGenZeroDb
1 - 100
PFHiHiLim
-1.000 - 1.000
PFHiLim
-1.000 - 1.000
PFLowLim
-1.000 - 1.000
PFLowLowLim
-1.000 - 1.000
PFLimHyst
0.000 - 100.000
UDbRepInt
1 - 300
UZeroDb
0 - 100000
UHiHiLim
0.0 - 200.0
UHiLim
0.0 - 200.0
ULowLim
0.0 - 200.0
ULowLowLim
0.0 - 200.0
ULimHyst
0.000 - 100.000
IDbRepInt
1 - 300
IZeroDb
0 - 100000
Table continues on next page
512
Unit
Step
Default
Type
1
10
m%
1
500
%SB
0.1
120.0
%SB
0.1
-120.0
%SB
0.1
-150.0
%
0.001
5.000
Type
1
10
m%
1
500
%SB
0.1
150.0
%SB
0.1
120.0
%SB
0.1
-120.0
%SB
0.1
-150.0
%
0.001
5.000
%VB
1
5
Type
1
10
m%
1
500
%IB
1
5
-
0.001
1.000
-
0.001
0.800
-
0.001
-0.800
-
0.001
-1.000
%
0.001
5.000
Type
1
10
m%
1
500
%VB
0.1
150.0
%VB
0.1
120.0
%VB
0.1
80.0
%VB
0.1
60.0
%
0.001
5.000
Type
1
10
m%
1
500
1MRK 502 048-UUS A
Description
Cycl: Report interval (s), Db: In % of range, Int
Db: In %s
Zero point clamping
High limit in % of SBase
Low limit in % of SBase
Low Low limit in % of SBase
Hysteresis value in % of range (common for all
limits)
Cycl: Report interval (s), Db: In % of range, Int
Db: In %s
Zero point clamping
High High limit in % of SBase
High limit in % of SBase
Low limit in % of SBase
Low Low limit in % of SBase
Hysteresis value in % of range (common for all
limits)
Zero point clamping in % of VBase
Cycl: Report interval (s), Db: In % of range, Int
Db: In %s
Zero point clamping
Zero point clamping in % of IBase
High High limit (physical value)
High limit (physical value)
Low limit (physical value)
Low Low limit (physical value)
Hysteresis value in % of range (common for all
limits)
Cycl: Report interval (s), Db: In % of range, Int
Db: In %s
Zero point clamping
High High limit in % of UBase
High limit in % of VBase
Low limit in % of VBase
Low Low limit in % of VBase
Hysteresis value in % of range (common for all
limits)
Cycl: Report interval (s), Db: In % of range, Int
Db: In %s
Zero point clamping
Technical manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

650 seriesReg650 ansi

Table of Contents