1MRK 502 048-UUS A
18.2.2
18.2.3
Technical manual
Auxiliary supply voltage input
The auxiliary voltage of the IED is connected to terminals X420-1 and X420-2/3. The
terminals used depend on the power supply.
The permitted auxiliary voltage range of the IED is marked on top of the IED's LHMI.
Table 532:
Auxiliary voltage supply of 110...250 V DC or 100...240 V AC
Case
3U full 19"
Table 533:
Auxiliary voltage supply of 48-125 V DC
Case
3U full 19"
Table 534:
Auxiliary voltage supply of 24-30 V DC
Case
3U full 19"
Binary inputs
The binary inputs can be used, for example, to generate a blocking signal, to unlatch output
contacts, to trigger the digital fault recorder or for remote control of IED settings.
Each signal connector terminal is connected with one 14 or 16 Gauge wire.
Table 535:
Binary inputs X304, 3U full 19"
Terminal
Description
X304-1
Common - for inputs 1-3
X304-2
Binary input 1 +
X304-3
Binary input 2 +
X304-4
Binary input 3 +
X304-5
Common - for inputs 4-6
Table continues on next page
IED physical connections
Terminal
X420-1
X420-3
Terminal
X420-1
X420-2
Terminal
X420-3
X420-2
Hardware module
instance
COM_101
COM_101
COM_101
Section 18
Description
- Input
+ Input
Description
- Input
+ Input
Description
- Input
+ Input
PCM600 info
Hardware channel
BI1
BI2
BI3