1MRK 502 048-UUS A
8.1.5
Table 85:
OC4PTOC (51_67) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
DirMode1
Disabled
Non-directional
Forward
Reverse
Characterist1
ANSI Ext. inv.
ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
RI type
RD type
I1>
5 - 2500
t1
0.000 - 60.000
k1
0.05 - 999.00
IMin1
5 - 10000
t1Min
0.000 - 60.000
Table continues on next page
Technical manual
Name
Type
ST1
BOOLEAN
ST2
BOOLEAN
ST3
BOOLEAN
ST4
BOOLEAN
STL1
BOOLEAN
STL2
BOOLEAN
STL3
BOOLEAN
ST2NDHRM
BOOLEAN

Settings

Unit
Step
-
-
-
-
-
-
%IB
1
s
0.001
-
0.01
%IB
1
s
0.001
Description
Pick up signal from step 1
Pick up signal from step 2
Pickup signal step 3
Pickup signal step 4
Pickup signal from phase A
Pickup signal from phase B
Pickup signal from phase C
Second harmonic detected
Default
Description
Disabled
Disable/Enable Operation
Non-directional
Directional mode of step 1 off / non-directional /
forward / reverse
ANSI Def. Time
Selection of time delay curve type for step 1
1000
Phase current operate level for step1 in % of
IBase
0.000
Definite time delay of step 1
0.05
Time multiplier for the inverse time delay for
step 1
100
Minimum operate current for step1in% of IBase
0.000
Minimum operate time for inverse curves for
step 1
Section 8
Current protection
195