Section 13
Logic
13.2.5
Table 299:
TMAGGIO Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
PulseTime
0.050 - 60.000
OnDelay
0.000 - 60.000
OffDelay
0.000 - 60.000
ModeOutput1
Steady
Pulsed
ModeOutput2
Steady
Pulsed
ModeOutput3
Steady
Pulsed
13.2.6
472
Table 298:
TMAGGIO Output signals
Name
Type
OUTPUT1
BOOLEAN
OUTPUT2
BOOLEAN
OUTPUT3
BOOLEAN

Settings

Unit
Step
-
-
s
0.001
s
0.001
s
0.001
-
-
-
-
-
-
Operation principle
The trip matrix logic (TMAGGIO) block is provided with 32 input signals and 3 output
signals. The function block incorporates internal logic OR gates in order to provide
grouping of connected input signals to the three output signals from the function block.
Internal built-in OR logic is made in accordance with the following three rules:
1.
when any one of first 16 inputs signals (INPUT1 to INPUT16) has logical value 1 the
first output signal (OUTPUT1) will get logical value 1.
2.
when any one of second 16 inputs signals (INPUT17 to INPUT32) has logical value
1 the second output signal (OUTPUT2) will get logical value 1.
3.
when any one of all 32 input signals (INPUT1 to INPUT32) has logical value 1 the
third output signal (OUTPUT3) will get logical value 1.
By use of the settings ModeOutput1, ModeOutput2, ModeOutput3, PulseTime, OnDelay
and OffDelay the behavior of each output can be customized. The OnDelay is always
active and will delay the input to output transition by the set time. The ModeOutput for
respective output decides whether the output shall be steady with an drop-off delay as set
Description
OR function betweeen inputs 1 to 16
OR function between inputs 17 to 32
OR function between inputs 1 to 32
Default
Description
Enabled
Operation Disable / Enable
0.150
Output pulse time
0.000
Output on delay time
0.000
Output off delay time
Steady
Mode for output 1, steady or pulsed
Steady
Mode for output 2, steady or pulsed
Steady
Mode for output 3, steady or pulsed