Section 13
Logic
13.3.1.2
476
INVALIDQT function which sets quality invalid of outputs according to a "valid"
input. Inputs are copied to outputs. If input VALID is 0, or if its quality invalid bit is
set, all outputs invalid quality bit will be set to invalid. The timestamp of an output
will be set to the latest timestamp of INPUT and VALID inputs.
INDCOMBSPQT combines single input signals to group signal. Single position
input is copied to value part of SP_OUT output. TIME input is copied to time part of
SP_OUT output. Quality input bits are copied to the corresponding quality part of
SP_OUT output.
INDEXTSPQT extracts individual signals from a group signal input. Value part of
single position input is copied to SI_OUT output. Time part of single position input
is copied to TIME output. Quality bits in common part and indication part of inputs
signal is copied to the corresponding quality output.

OR function block

Identification
Function description
OR Function block
Functionality
The OR function is used to form general combinatory expressions with boolean variables.
The OR function block has six inputs and two outputs. One of the outputs is inverted.
Function block
OR
INPUT1
OUT
INPUT2
NOUT
INPUT3
INPUT4
INPUT5
INPUT6
IEC09000288-1-en.vsd
IEC09000288 V1 EN
Figure 217:
OR function block
IEC 61850
IEC 60617
identification
identification
OR
-
1MRK 502 048-UUS A
ANSI/IEEE C37.2
device number
-
Technical manual