ABB Relion Technical Manual page 535

Generator protection
Hide thumbs Also See for Relion:
Table of Contents

Advertisement

1MRK 502 048-UUS A
Y
Value Reported
(1st)
(*)Set value for t: XDbRepInt
IEC05000500 V1 EN
Figure 242:
Periodic reporting
Technical manual
Actual value of the measured quantity
The actual value of the measured quantity is available locally and remotely. The
measurement is continuous for each measured quantity separately, but the reporting of the
value to the higher levels depends on the selected reporting mode. The following basic
reporting modes are available:
Cyclic reporting (Cyclic)
Magnitude dead-band supervision (Dead band)
Integral dead-band supervision (Int deadband)
Cyclic reporting
The cyclic reporting of measured value is performed according to chosen setting
(XRepTyp). The measuring channel reports the value independent of magnitude or
integral dead-band reporting.
In addition to the normal cyclic reporting the IED also report spontaneously when
measured value passes any of the defined threshold limits.
Value Reported
Y2
Y1
t (*)
Value Reported
Y3
Y4
t (*)
t (*)
Section 14
Monitoring
Value Reported
Value Reported
Y5
t (*)
en05000500.vsd
t
529