Section 7
Impedance protection
7.1.4
7.1.5
Table 52:
ZMRPSB (68) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
X1InFw
0.10 - 3000.00
R1LIn
0.10 - 1000.00
R1FInFw
0.10 - 1000.00
X1InRv
0.10 - 3000.00
R1FInRv
0.10 - 1000.00
OperationLdCh
Disabled
Enabled
RLdOutFw
0.10 - 3000.00
ArgLd
5 - 70
RLdOutRv
0.10 - 3000.00
Table continues on next page
152

Signals

Table 50:
ZMRPSB (68) Input signals
Name
Type
I3P
GROUP
SIGNAL
U3P
GROUP
SIGNAL
BLOCK
BOOLEAN
BLKI01
BOOLEAN
BLKI02
BOOLEAN
I0CHECK
BOOLEAN
EXTERNAL
BOOLEAN
Table 51:
ZMRPSB (68) Output signals
Name
Type
START
BOOLEAN
ZOUT
BOOLEAN
ZIN
BOOLEAN
Settings
Unit
Step
-
-
ohm
0.01
ohm
0.01
ohm
0.01
ohm
0.01
ohm
0.01
-
-
ohm
0.01
Deg
1
ohm
0.01
Default
Description
-
Three phase group signal for current inputs
-
Three phase group signal for voltage inputs
0
Block of function
0
Block inhibit of start output for slow swing condition
0
Block inhibit of start output for subsequent residual
current detect
0
Residual current (3I0) detection to inhibit start output
0
Input for external detection of power swing
Description
Power swing detected
Measured impedance within outer impedance boundary
Measured impedance within inner impedance boundary
Default
Description
Disabled
Disbled/Enabled operation
30.00
Inner reactive boundary, forward
30.00
Line resistance for inner characteristic angle
30.00
Fault resistance coverage to inner resistive
line, forward
30.00
Inner reactive boundary, reverse
30.00
Fault resistance line to inner resistive
boundary, reverse
Enabled
Operation of load discrimination characteristic
30.00
Outer resistive load boundary, forward
25
Load angle determining load impedance area
30.00
Outer resistive load boundary, reverse
1MRK 502 048-UUS A
Technical manual