Adaptive frequency tracking is included to ensure proper operation of the generator
differential protection during varying frequency conditions.
An open CT circuit condition creates unexpected operations for Generator differential
protection under the normal load conditions. It is also possible to damage secondary
equipment due to high voltage produced from open CT circuit outputs. Therefore, it may
be a requirement from security and reliability points of view to have open CT detection
function to block Generator differential protection function in case of open CT conditions
and at the same time produce the alarm signal to the operational personal to make quick
remedy actions to correct the open CT condition.
Generator differential protection GENPDIF (87G) is also well suited to generate fast,
sensitive and selective fault clearance, if used to protect shunt reactors or small busduct.

Function block

GENPDIF (87G)
I3PNCT*
TRIP
I3PTCT*
TRIPRES
BLOCK
TRIPUNRE
BLKRES
TRNSUNR
BLKUNRES
TRNSSENS
BLKNSUNR
PICKUP
BLKNSSEN
BLKH
DESENSIT
OPENCT
OPENCTAL
IDMAG_A
IDMAG_B
IDMAG_C
IDMAG_NS
IBIAS
ANSI07000025-2-en.vsd
ANSI07000025 V3 EN
Figure 49:
GENPDIF (87G) function block
Signals
Table 44:
GENPDIF (87G) Input signals
Name
Type
I3PNCT
GROUP
SIGNAL
I3PTCT
GROUP
SIGNAL
BLOCK
BOOLEAN
BLKRES
BOOLEAN
BLKUNRES
BOOLEAN
Table continues on next page
Default
Description
-
Neutral side CT input
-
Terminal side CT input
0
Block of function
0
Block of trip from the restrained diff. protection
0
Block of trip from unrestrained diff. prot.
Section 6
Differential protection