ABB Relion Technical Manual page 540

Generator protection
Hide thumbs Also See for Relion:
Table of Contents

Advertisement

Section 14
Monitoring
534
Each analog output has a corresponding supervision level output (X_RANGE). The
output signal is an integer in the interval 0-4, see section
Calibration of analog inputs
Measured currents and voltages used in the CVMMXN function can be calibrated to get
class 0.5 measuring accuracy. This is achieved by magnitude and angle compensation at
5, 30 and 100% of rated current and voltage. The compensation below 5% and above
100% is constant and linear in between, see example in figure 245.
Magnitude
% of In
compensation
+10
IMagComp5
IMagComp30
IMagComp100
5
-10
Angle
Degrees
compensation
+10
IAngComp30
IAngComp5
IAngComp100
5
-10
ANSI05000652 V3 EN
Figure 245:
Calibration curves
The first current and voltage phase in the group signals will be used as reference and the
magnitude and angle compensation will be used for related input signals.
Low pass filtering
In order to minimize the influence of the noise signal on the measurement it is possible to
introduce the recursive, low pass filtering of the measured values for P, Q, S, V, I and
power factor. This will make slower measurement response to the step changes in the
30
0-5%:
Constant
5-30-100%: Linear
>100%:
Constant
30
1MRK 502 048-UUS A
"Measurement
supervision".
Measured
current
100
% of In
Measured
current
100
% of In
ANSI05000652_3_en.vsd
Technical manual