Settings - ABB Relion Technical Manual

Generator protection
Hide thumbs Also See for Relion:
Table of Contents

Advertisement

Section 12
Control
12.5.5
Table 269:
VSGGIO Non group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
CtlModel
Dir Norm
SBO Enh
Mode
Steady
Pulsed
tSelect
0.000 - 60.000
tPulse
0.000 - 60.000
12.5.6
452
Table 268:
VSGGIO Output signals
Name
Type
BLOCKED
BOOLEAN
POSITION
INTEGER
POS1
BOOLEAN
POS2
BOOLEAN
CMDPOS12
BOOLEAN
CMDPOS21
BOOLEAN

Settings

Unit
Step
-
-
-
-
-
-
s
0.001
s
0.001
Operation principle
Selector mini switch (VSGGIO) function can be used for double purpose, in the same way
as switch controller (SCSWI) functions are used:
for indication on the single line diagram (SLD). Position is received through the
IPOS1 and IPOS2 inputs and distributed in the configuration through the POS1 and
POS2 outputs, or to IEC 61850 through reporting, or GOOSE.
for commands that are received via the local HMI or IEC 61850 and distributed in the
configuration through outputs CMDPOS12 and CMDPOS21.
The output CMDPOS12 is set when the function receives a CLOSE command from
the local HMI when the SLD is displayed and the object is chosen.
The output CMDPOS21 is set when the function receives an OPEN command from
the local HMI when the SLD is displayed and the object is chosen.
Description
The function is active but the functionality is blocked
Position indication, integer
Position 1 indication, logical signal
Position 2 indication, logical signal
Execute command from position 1 to position 2
Execute command from position 2 to position 1
Default
Description
Disabled
Disable/Enable Operation
Dir Norm
Specifies the type for control model according
to IEC 61850
Pulsed
Operation mode
30.000
Max time between select and execute signals
0.200
Command pulse lenght
1MRK 502 048-UUS A
Technical manual