Settings - ABB Relion Technical Manual

Generator protection
Hide thumbs Also See for Relion:
Table of Contents

Advertisement

1MRK 502 048-UUS A
8.10.5
Table 149:
VRPVOC (51V) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
StartCurr
2.0 - 5000.0
Characterist
ANSI Ext. inv.
ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
tDef_OC
0.00 - 6000.00
k
0.05 - 999.00
tMin
0.00 - 6000.00
Operation_UV
Disabled
Enabled
StartVolt
2.0 - 100.0
tDef_UV
0.00 - 6000.00
EnBlkLowV
Disabled
Enabled
BlkLowVolt
0.0 - 5.0
Table 150:
VRPVOC (51V) Group settings (advanced)
Name
Values (Range)
VDepFact
5.0 - 100.0
VDepMode
Step
Slope
UHighLimit
30.0 - 100.0
Technical manual

Settings

Unit
Step
-
-
%IB
1.0
-
-
s
0.01
-
0.01
s
0.01
-
-
%VB
0.1
s
0.01
-
-
%VB
0.1
Unit
Step
-
0.1
-
-
%VB
0.1
Default
Description
Disabled
Disable/Enable Operation
120.0
Pick up current level in % of IBase
IEC Norm. inv.
Time delay curve type for 51V
0.50
Independent (definite) time delay for OC
1.00
Time multiplier for the IDMT curves
0.05
Minimum operate time for IDMT curves
Disabled
Operation of under-voltage stage (ANSI 27)
Off / On
50.0
Operate undervoltage level for UV in % of
Vbase
1.00
Operate time delay in sec for definite time use
of UV
Disabled
Enable internal low voltage level blocking for
UV
3.0
Internal low voltage blocking level for UV in %
of Vbase
Default
Description
25.0
Pick up current level in % of pickup when V<
25% of VBase
Slope
Voltage dependent mode OC (step, slope)
100.0
Voltage high limit setting in % of Vbase
Section 8
Current protection