Synchronizing

When the function is set to OperationSynch = Enabled the measuring will be performed.
The function will compare the values for the bus and line voltage with internally preset
values that are set to be 80% of the set UBase selected for GlbBaseSelBus and
GlbBaseSelLine, which is a supervision that the voltages are both live. Also the voltage
difference is checked to be smaller than the internally preset value 0.10, which is a p.u
value of set voltage base values. If both sides are higher than the preset values and the
Note! Similar logic for Manual Synchrocheck.
AND
AND
0-tSCA
0
50 ms
0
0
AND
80 ms
PhaseDiff > 60°
PhaseDiff < 5°