Monitored Data - ABB Relion Technical Manual

Generator protection
Hide thumbs Also See for Relion:
Table of Contents

Advertisement

1MRK 502 048-UUS A
14.14.7
14.14.8
Technical manual

Monitored Data

Table 418:
SPVNZBAT Monitored data
Name
Type
BATTVOLT
REAL
Operation principle
The function can be enabled and disabled with the Operation setting. The corresponding
parameter values are Enable and Disable.
The function execution requires that at least one of the function outputs is
connected in configuration.
The operation of the station battery supervision function can be described by using a
module diagram. All the modules in the diagram are explained in the next sections.
Comparator
V<BattVoltLowLim
V_BATT
Comparator
U<BattVoltHiLim
ANSI11000292 V1 EN
Figure 261:
Functional module diagram
The battery rated voltage is set with the RtdBattVolt setting. The value of the
BattVoltLowLim and BattVoltHiLim settings are given in relative per unit to the
RtdBattVolt setting.
It is possible to block the function outputs by the BLOCK input.
Low level detector
The level detector compares the battery voltage V_BATT with the set value of the
BattVoltLowLim setting. If the value of the V_BATT input drops below the set value of the
BattVoltLowLim setting, the pickup signal PU_VLOW is activated.
Values (Range)
Unit
-
kV
0
0-tReset
0
0-tReset
Section 14
Monitoring
Description
Service value of the battery
terminal voltage
PU_VLOW
0-tDelay
AL_VLOW
0
PU_VHI
0-tDelay
AL_VHI
0
ANSI11000292-1-en.vsd
595