Time Synchronization Via Irig-B - ABB Relion Technical Manual

Generator protection
Hide thumbs Also See for Relion:
Table of Contents

Advertisement

Section 17
Basic IED functions
17.2.7
17.2.7.1
17.2.7.2
Table 497:
IRIG-B Non group settings (basic)
Name
Values (Range)
TimeDomain
LocalTime
UTC
Encoding
IRIG-B
1344
1344TZ
TimeZoneAs1344
MinusTZ
PlusTZ
17.2.8
17.2.8.1
672

Time synchronization via IRIG-B

Identification
Function description
Time synchronization via IRIG-B
Settings
Unit
Step
-
-
-
-
-
-
Operation principle
General concepts
Time definitions
The error of a clock is the difference between the actual time of the clock, and the time the
clock is intended to have. Clock accuracy indicates the increase in error, that is, the time
gained or lost by the clock. A disciplined clock knows its own faults and tries to
compensate for them.
IEC 61850
IEC 60617
identification
identification
IRIG-B
-
Default
Description
LocalTime
Time domain
IRIG-B
Type of encoding
PlusTZ
Time zone as in 1344 standard
1MRK 502 048-UUS A
ANSI/IEEE C37.2
device number
-
Technical manual

Advertisement