Section 12
Control
Name
Values (Range)
AutoEnerg
Disabled
DLLB
DBLL
Both
ManEnerg
Disabled
DLLB
DBLL
Both
ManEnergDBDL
Disabled
Enabled
tAutoEnerg
0.000 - 60.000
tManEnerg
0.000 - 60.000
Table 211:
SESRSYN (25) Non group settings (basic)
Name
Values (Range)
GblBaseSelBus
1 - 6
GblBaseSelLine
1 - 6
SelPhaseBus1
Phase L1
Phase L2
Phase L3
Phase L1L2
Phase L2L3
Phase L3L1
Positive sequence
SelPhaseBus2
Phase L1
Phase L2
Phase L3
Phase L1L2
Phase L2L3
Phase L3L1
Positive sequence
SelPhaseLine1
Phase L1
Phase L2
Phase L3
Phase L1L2
Phase L2L3
Phase L3L1
Positive sequence
SelPhaseLine2
Phase L1
Phase L2
Phase L3
Phase L1L2
Phase L2L3
Phase L3L1
Positive sequence
350
Unit
Step
Default
-
-
DLLB
-
-
Both
-
-
Disabled
s
0.001
0.100
s
0.001
0.100
Unit
Step
Default
-
1
1
-
1
1
-
-
Phase L1
-
-
Phase L1
-
-
Phase L1
-
-
Phase L1
1MRK 502 048-UUS A
Description
Automatic energizing check mode
Manual energizing check mode
Manual dead bus, dead line energizing
Time delay for automatic energizing check
Time delay for manual energizing check
Description
Selection of one of the Global Base Value
groups, Bus
Selection of one of the Global Base Value
groups, Line
Select phase for busbar1
Select phase for busbar2
Select phase for line1
Select phase for line2
Technical manual