Signals - ABB Relion Technical Manual

Generator protection
Hide thumbs Also See for Relion:
Table of Contents

Advertisement

Section 15
Metering
15.1.4
15.1.5
Table 451:
PCGGIO Non group settings (basic)
Name
Values (Range)
Operation
Off
On
EventMask
NoEvents
ReportEvents
CountCriteria
Off
RisingEdge
Falling edge
OnChange
Scale
1.000 - 90000.000
Quantity
Count
ActivePower
ApparentPower
ReactivePower
ActiveEnergy
ApparentEnergy
ReactiveEnergy
tReporting
1 - 3600
630

Signals

Table 449:
PCGGIO Input signals
Name
Type
BLOCK
BOOLEAN
READ_VAL
BOOLEAN
BI_PULSE
BOOLEAN
RS_CNT
BOOLEAN
Table 450:
PCGGIO Output signals
Name
Type
INVALID
BOOLEAN
RESTART
BOOLEAN
BLOCKED
BOOLEAN
NEW_VAL
BOOLEAN
SCAL_VAL
REAL
Settings
Unit
Step
-
-
-
-
-
-
-
0.001
-
-
s
1
Default
Description
0
Block of function
0
Initiates an additional pulse counter reading
0
Connect binary input channel for metering
0
Resets pulse counter value
Description
The pulse counter value is invalid
The reported value does not comprise a complete
integration cycle
The pulse counter function is blocked
A new pulse counter value is generated
Scaled value with time and status information
Default
Description
Off
Operation Off/On
NoEvents
Report mask for analog events from pulse
counter
RisingEdge
Pulse counter criteria
1.000
Scaling value for SCAL_VAL output to unit per
counted value
Count
Measured quantity for SCAL_VAL output
60
Cycle time for reporting of counter value
1MRK 502 048-UUS A
Technical manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

650 seriesReg650 ansi

Table of Contents