Status For User Defined Signals For Iec 60870-5-103 I103Usrdef - ABB Relion Technical Manual

Generator protection
Hide thumbs Also See for Relion:
Table of Contents

Advertisement

1MRK 502 048-UUS A
14.25
14.25.1
14.25.2
Technical manual
Status for user defined signals for IEC 60870-5-103
I103USRDEF
Functionality
I103USRDEF is a function blocks with user defined input signals in monitor direction.
These function blocks include the FunctionType parameter for each block in the private
range, and the information number parameter for each input signal.
I103USRDEF can be used, for example in mapping the INF numbers not supported
directly by specific function blocks, like: INF17, INF18, INF20 or INF35. After
connecting the appropriate signals to the I103USRDEF inputs, the user must also set the
InfNo_x values in the settings.
GUID-391D4145-B7E6-4174-B3F7-753ADDA4D06F V1 EN
Figure 283:
IEC 60870-5-103I103USRDEF:1
Function block
I103USRDEF
BLOCK
^INPUT1
^INPUT2
^INPUT3
^INPUT4
^INPUT5
^INPUT6
^INPUT7
^INPUT8
IEC10000294-1-en.vsd
IEC10000294 V1 EN
Figure 284:
I103USRDEF function block
Section 14
Monitoring
627