ABB Relion Technical Manual page 590

Generator protection
Hide thumbs Also See for Relion:
Table of Contents

Advertisement

Section 14
Monitoring
584
The header file (optional in the standard) contains basic information about the
disturbance, that is, information from the Disturbance report sub-functions. The
Disturbance handling tool use this information and present the recording in a user-friendly
way.
General:
Station name, object name and unit name
Date and time for the trig of the disturbance
Record number
Sampling rate
Time synchronization source
Recording times
Activated trig signal
Active setting group
Analog:
Signal names for selected analog channels
Information e.g. trig on analog inputs
Primary and secondary instrument transformer rating
Over- or Undertrig: level and operation
Over- or Undertrig status at time of trig
CT direction
Binary:
Signal names
Status of binary input signals
The configuration file is a mandatory file containing information needed to interpret the
data file. For example sampling rate, number of channels, system frequency, channel info
etc.
The data file, which also is mandatory, containing values for each input channel for each
sample in the record (scaled value). The data file also contains a sequence number and
time stamp for each set of samples.
1MRK 502 048-UUS A
Technical manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

650 seriesReg650 ansi

Table of Contents