Settings - ABB Relion Technical Manual

Generator protection
Hide thumbs Also See for Relion:
Table of Contents

Advertisement

1MRK 502 048-UUS A
8.7.3.4
Table 129:
GUPPDUP (37) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
OpMode1
Disabled
UnderPower
Power1
0.0 - 500.0
Angle1
-180.0 - 180.0
TripDelay1
0.010 - 6000.000
OpMode2
Disabled
UnderPower
Power2
0.0 - 500.0
Angle2
-180.0 - 180.0
TripDelay2
0.010 - 6000.000
Table 130:
GUPPDUP (37) Group settings (advanced)
Name
Values (Range)
TD
0.00 - 0.99
Technical manual
Name
Type
PICKUP1
BOOLEAN
PICKUP2
BOOLEAN
P
REAL
PPERCENT
REAL
Q
REAL
QPERCENT
REAL

Settings

Unit
Step
-
-
-
-
%
0.1
Deg
0.1
s
0.001
-
-
%
0.1
Deg
0.1
s
0.001
Unit
Step
-
0.01
Description
Pickup signal from stage 1
Pickup signal from stage 2
Active Power
Active power in % of calculated power base value
Reactive power
Reactive power in % of calculated power base value
Default
Description
Disabled
Operation Disable / Enable
UnderPower
Operation mode 1
1.0
Power setting for stage 1 in % of calculated
power base value
0.0
Characteristic angle for stage 1
1.000
Trip delay for stage 1
UnderPower
Operation mode 2
1.0
Power setting for stage 2 in % of calculated
power base value
0.0
Characteristic angle for stage 2
1.000
Trip delay for stage 2
Default
Description
0.00
Low pass filter coefficient for power
measurement, V and I
Section 8
Current protection
257