Electromagnetic Compatibility Tests - ABB Relion Technical Manual

Generator protection
Hide thumbs Also See for Relion:
Table of Contents

Advertisement

1MRK 502 048-UUS A
Section 20
20.1
Technical manual
IED and functionality tests

Electromagnetic compatibility tests

Table 569:
Electromagnetic compatibility tests
Description
100 kHz and 1 MHz burst
disturbance test
Common mode
Differential mode
Electrostatic discharge test
Contact discharge
Air discharge
Radio frequency interference
tests
Conducted, common mode
Radiated, amplitude-
modulated
Fast transient disturbance tests
Communication ports
Other ports
Surge immunity test
Communication
Other ports
Power supply
Table continues on next page
IED and functionality tests
Type test value
2.5 kV
2.5 kV
8 kV
15 kV
10 V (emf), f=150 kHz...80 MHz
20 V/m (rms), f=80...1000 MHz
and f=1.4...2.7 GHz
4 kV
4 kV
1 kV line-to-ground
2 kV line-to-ground, 1 kV line-to-
line
4 kV line-to-ground, 2 kV line-to-
line
Section 20
Reference
IEC 61000-4-18, level 3
IEC 60255-22-1
ANSI C37.90.1-2012
IEC 61000-4-2, level 4
IEC 60255-22-2
ANSI C37.90.3-2001
IEC 61000-4-6 , level 3
IEC 60255-22-6
IEC 61000-4-3, level 3
IEC 60255-22-3
ANSI C37.90.2-2004
IEC 61000-4-4
IEC 60255-22-4, class A
ANSI C37.90.1-2012
IEC 61000-4-5
IEC 60255-22-5
729

Advertisement

Table of Contents
loading

This manual is also suitable for:

650 seriesReg650 ansi

Table of Contents