Settings - ABB Relion Technical Manual

Generator protection
Hide thumbs Also See for Relion:
Table of Contents

Advertisement

Section 12
Control
12.2.2.5
Table 216:
SCSWI Non group settings (basic)
Name
Values (Range)
CtlModel
Dir Norm
SBO Enh
PosDependent
Always permitted
Not perm at 00/11
tSelect
0.000 - 60.000
tSynchrocheck
0.00 - 600.00
tSynchronizing
0.00 - 600.00
tExecutionFB
0.00 - 600.00
12.2.3
12.2.3.1
364
Name
Type
POSITION
INTEGER
OPENPOS
BOOLEAN
CLOSEPOS
BOOLEAN
CMD_BLK
BOOLEAN
L_CAUSE
INTEGER
POS_INTR
BOOLEAN
XOUT
BOOLEAN

Settings

Unit
Step
-
-
-
-
s
0.001
s
0.01
s
0.01
s
0.01
Circuit breaker SXCBR
Signals
Table 217:
SXCBR Input signals
Name
Type
BLOCK
BOOLEAN
LR_SWI
BOOLEAN
OPEN
BOOLEAN
CLOSE
BOOLEAN
BL_OPEN
BOOLEAN
BL_CLOSE
BOOLEAN
BL_UPD
BOOLEAN
Table continues on next page
Description
Position indication
Open position indication
Closed position indication
Commands are blocked
Latest value of the error indication during command
Stopped in intermediate position
Execution information to XCBR/XSWI
Default
Description
SBO Enh
Specifies control model type
Always permitted
Permission to operate depending on the
position
30.000
Maximum time between select and execute
signals
10.00
Allowed time for synchronism-check to fulfil
close conditions
0.00
Supervision time to get the signal
synchronizing in progress
30.00
Maximum time from command execution to
termination
Default
Description
0
Block of function
0
Local/Remote switch indication from switchyard
0
Pulsed signal used to immediately open the switch
0
Pulsed signal used to immediately close the switch
0
Signal to block the open command
0
Signal to block the close command
0
Steady signal for block of the position updating
1MRK 502 048-UUS A
Technical manual

Advertisement

Table of Contents
loading

This manual is also suitable for: