Generator protection
Hide thumbs Also See for Relion:
Table of Contents

Advertisement

1MRK 502 048-UUS A
Name
Values (Range)
PMax
-2000.0 - 2000.0
PRepTyp
Cyclic
Dead band
Int deadband
QMin
-2000.0 - 2000.0
QMax
-2000.0 - 2000.0
QRepTyp
Cyclic
Dead band
Int deadband
PFMin
-1.000 - 1.000
PFMax
-1.000 - 1.000
PFRepTyp
Cyclic
Dead band
Int deadband
UMin
0.0 - 200.0
UMax
0.0 - 200.0
URepTyp
Cyclic
Dead band
Int deadband
IMin
0.0 - 500.0
IMax
0.0 - 500.0
IRepTyp
Cyclic
Dead band
Int deadband
FrMin
0.000 - 100.000
FrMax
0.000 - 100.000
FrRepTyp
Cyclic
Dead band
Int deadband
Table 348:
CVMMXN Non group settings (advanced)
Name
Values (Range)
SDbRepInt
1 - 300
SZeroDb
0 - 100000
SHiHiLim
0.0 - 2000.0
SHiLim
0.0 - 2000.0
PHiHiLim
-2000.0 - 2000.0
SLimHyst
0.000 - 100.000
Table continues on next page
Technical manual
Unit
Step
Default
%SB
0.1
200.0
-
-
Cyclic
%SB
0.1
-200.0
%SB
0.1
200.0
-
-
Cyclic
-
0.001
-1.000
-
0.001
1.000
-
-
Cyclic
%VB
0.1
50.0
%VB
0.1
200.0
-
-
Cyclic
%IB
0.1
50.0
%IB
0.1
200.0
-
-
Cyclic
Hz
0.001
0.000
Hz
0.001
70.000
-
-
Cyclic
Unit
Step
Default
Type
1
10
m%
1
500
%SB
0.1
150.0
%SB
0.1
120.0
%SB
0.1
150.0
%
0.001
5.000
Section 14
Monitoring
Description
Maximum value in % of SBase
Reporting type
Minimum value in % of SBase
Maximum value in % of SBase
Reporting type
Minimum value
Maximum value
Reporting type
Minimum value in % ofVUBase
Maximum value in % of VBase
Reporting type
Minimum value in % of IBase
Maximum value in % of IBase
Reporting type
Minimum value
Maximum value
Reporting type
Description
Cycl: Report interval (s), Db: In % of range, Int
Db: In %s
Zero point clamping in 0.001% of range
High High limit in % of SBase
High limit in % of SBase
High High limit in % of SBase
Hysteresis value in % of range (common for all
limits)