Signals - ABB Relion Technical Manual

Generator protection
Hide thumbs Also See for Relion:
Table of Contents

Advertisement

1MRK 502 048-UUS A
7.2.4
7.2.5
Table 58:
ZGCPDIS (21G) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
ImpedanceAng
0.00 - 90.00
OpModeZ1
Disable-Zone
Enable-Zone
Z1Fwd
0.005 - 3000.000
Z1Rev
0.005 - 3000.000
tZ1
0.000 - 60.000
OpModeZ2
Disable-Zone
Enable-Zone
Z2Fwd
0.005 - 3000.000
Table continues on next page
Technical manual

Signals

Table 56:
ZGCPDIS (21G) Input signals
Name
Type
I3P
GROUP
SIGNAL
V3P
GROUP
SIGNAL
BLOCK
BOOLEAN
BLKZ
BOOLEAN
LDCND
INTEGER
Table 57:
ZGCPDIS (21G) Output signals
Name
Type
TRIP
BOOLEAN
TRZ1
BOOLEAN
TRZ2
BOOLEAN
TRZ3
BOOLEAN
PICKUP
BOOLEAN
PU_Z1
BOOLEAN
PU_Z2
BOOLEAN
Z3_PU
BOOLEAN
Settings
Unit
Step
-
-
Deg
0.01
-
-
ohm/p
0.001
ohm/p
0.001
s
0.001
-
-
ohm/p
0.001
Default
Description
-
Three phase group signal for current
-
Three phase group signal for voltage
0
Block of function
0
Block due to Fuse Fail
56
Load enchroachment binary coded release
Description
General trip
Trip signal Zone1
Trip signal Zone2
Trip signal Zone3
Pickup
Start signal Zone1
Start signal Zone2
Start signal Zone3
Default
Description
Disabled
Disable/Enable Operation
80.00
Impedance angle in degrees, common for all
zones
Disable-Zone
Operation mode of Zone 1
30.000
Forward reach setting for Zone 1
30.000
Reverse reach setting for Zone 1
0.100
Time delay to operate for Zone 1
Disable-Zone
Operation mode of Zone 2
30.000
Forward reach setting for Zone 2
Section 7
Impedance protection
161