Section 9
Voltage protection
9.2.7.3
9.2.7.4
292
The highest phase (or phase-to-phase) voltage is always used for the inverse time delay
integration, see
Figure
134. The details of the different inverse time characteristics are
shown in section
"Inverse time
Voltage
VA
VB
VC
ANSI05000016 V2 EN
Figure 134:
Voltage used for the inverse time characteristic integration
A TRIP requires that the overvoltage condition continues for at least the user set time
delay. This time delay is set by the parameter t1 and t2 for definite time mode (DT) and by
selected voltage level dependent time curves for the inverse time mode (TOV). If the
PICKUP condition, with respect to the measured voltage ceases during the delay time, the
corresponding PICKUP output is reset.

Blocking

It is possible to block two step overvoltage protection (OV2PTOV ,59) partially or
completely, by binary input signals where:
BLOCK:
BLK1:
BLK2:
Design
The voltage measuring elements continuously measure the three phase-to-ground
voltages or the three phase-to-phase voltages. Recursive Fourier filters or true RMS filters
of input voltage signals are used. The phase voltages are individually compared to the set
characteristics".
blocks all outputs
blocks all pickup and trip outputs related to step 1
blocks all pickup and trip outputs related to step 2
1MRK 502 048-UUS A
IDMT Voltage
Time
ANSI05000016-2-en.vsd
Technical manual