1MRK 502 048-UUS A
Name
Values (Range)
OperationZ2
Disabled
Enabled
XoffsetZ2
-1000.00 - 1000.00
Z2diameter
0.01 - 3000.00
tZ2
0.00 - 6000.00
Table 65:
LEXPDIS (40) Group settings (advanced)
Name
Values (Range)
DirSuperv
Disabled
Enabled
XoffsetDirLine
-1000.00 - 3000.00
DirAngle
-180.0 - 180.0
Table 66:
LEXPDIS (40) Non group settings (basic)
Name
Values (Range)
GlobalBaseSel
1 - 6
Table 67:
LEXPDIS (40) Non group settings (advanced)
Name
Values (Range)
InvertCTCurr
No
Yes
7.3.6
Technical manual
Unit
Step
-
-
%
0.01
%
0.01
s
0.01
Unit
Step
-
-
%
0.01
Deg
0.1
Unit
Step
-
1
Unit
Step
-
-
Monitored data
Table 68:
LEXPDIS (40) Monitored data
Name
Type
XOHM
REAL
XPERCENT
REAL
ROHM
REAL
RPERCENT
REAL
Default
Description
Enabled
Operation Disable/Enable zone Z2
-10.00
Offset of Z2 circle top point along X axis in % of
Zbase
200.00
Diameter of imedance circle for Z2 in % of
Zbase
1.00
Trip time delay for Z2
Default
Description
Disabled
Operation Off/On for additional directional
criterion
0.00
Offset of directional line along X axis in % of
Zbase
-13.0
Angle between directional line and R-axis in
degrees
Default
Description
1
Selection of one of the Global Base Value
groups
Default
Description
No
Invert current direction
Values (Range)
Unit
-
Ohm
-
%
-
Ohm
-
%
Section 7
Impedance protection
Description
Reactance in Primary Ohms
Reactance in percent of Zbase
Resistance in Primary Ohms
Resistance in percent of
Zbase
169