Setting Parameters For Communication Module - ABB Relion Technical Manual

Generator protection
Hide thumbs Also See for Relion:
Table of Contents

Advertisement

1MRK 502 048-UUS A
Name
Values (Range)
Threshold6
6 - 900
DebounceTime6
0.000 - 0.100
OscillationCount6
0 - 255
OscillationTime6
0.000 - 600.000
Threshold7
6 - 900
DebounceTime7
0.000 - 0.100
OscillationCount7
0 - 255
OscillationTime7
0.000 - 600.000
Threshold8
6 - 900
DebounceTime8
0.000 - 0.100
DebounceTime8
0 - 255
OscillationTime8
0.000 - 600.000
Threshold9
6 - 900
DebounceTime9
0.000 - 0.100
OscillationCount9
0 - 255
OscillationTime9
0.000 - 600.000
4.1.3.2
Table 10:
COM05_12BI Non group settings (basic)
Name
Values (Range)
BatteryVoltage
24 - 250
Table 11:
COM05_12BI Non group settings (advanced)
Name
Values (Range)
Threshold1
6 - 900
DebounceTime1
0.000 - 0.100
OscillationCount1
0 - 255
OscillationTime1
0.000 - 600.000
Threshold2
6 - 900
DebounceTime2
0.000 - 0.100
OscillationCount2
0 - 255
Table continues on next page
Technical manual
Unit
Step
%VB
1
s
0.001
-
1
s
0.001
%VB
1
s
0.001
-
1
s
0.001
%VB
1
s
0.001
-
1
s
0.001
%VB
1
s
0.001
-
1
s
0.001

Setting parameters for communication module

Unit
Step
V
1
Unit
Step
%VB
1
s
0.001
-
1
s
0.001
%VB
1
s
0.001
-
1
Binary input and output modules
Default
Description
65
Threshold in percentage of station battery
voltage for input 6
0.005
Debounce time for input 6
0
Oscillation count for input 6
0.000
Oscillation time for input 6
65
Threshold in percentage of station battery
voltage for input 7
0.005
Debounce time for input 7
0
Oscillation count for input 7
0.000
Oscillation time for input 7
65
Threshold in percentage of station battery
voltage for input 8
0.005
Debounce time for input 8
0
Oscillation count for input 8
0.000
Oscillation time for input 8
65
Threshold in percentage of station battery
voltage for input 9
0.005
Debounce time for input 9
0
Oscillation count for input 9
0.000
Oscillation time for input 9
Default
Description
110
Station battery voltage
Default
Description
65
Threshold in percentage of station battery
voltage for input 1
0.005
Debounce time for input 1
0
Oscillation count for input 1
0.000
Oscillation time for input 1
65
Threshold in percentage of station battery
voltage for input 2
0.005
Debounce time for input 2
0
Oscillation count for input 2
Section 4
59