08/2005
- The NC switches to follow-up mode.
- Channel not ready.
- NC Start disable in this channel.
- Interface signals are set.
- Alarm display.
- NC Stop on alarm.
Remedy:
Please inform the authorized personnel/service department.
Select MD 13010 DRIVE_LOGIC_NR and search for the drive logic number that is indi-
cated in the alarm text. The location index number + 1 results in the associated rack loca-
tion number. The FDD/MSD module belonging to this location is determined by the
configuration in MD 13040 DRIVE_TYPE for the same location index.
FDD: identifier 1, MSD: identifier 2.
Program Con-
Switch control OFF - ON.
tinuation:
300005
At least one module found on drive bus that has not been configured
Definitions:
At bus initialization at least one module was detected which did not have a drive number,
which amounts to one too many. Since all (!) modules on the drive bus must be correctly
initialized, all modules therefore also have to be accordingly specified in the machine
data.
Reactions:
- NC not ready.
- The NC switches to follow-up mode.
- Channel not ready.
- NC Start disable in this channel.
- Interface signals are set.
- Alarm display.
- NC Stop on alarm.
Remedy:
Please inform the authorized personnel/service department. Check machine data; with
the NCK MD 13000 DRIVE_IS_ACTIVE a drive that is not yet in use but exists on the bus
can be declared as inactive. Inactive drives do not need installation and start-up or drive
data.
Program Con-
Switch control OFF - ON.
tinuation:
300006
Module with drive number %1 has not been found on drive bus
Parameters:
%1 = Drive number
Definitions:
Not all of the drives stated in MD $MN_DRIVE_LOGIC_NR could be found on the drive
bus. You can find the associated module in the configuration display via the displayed
drive number.
Reactions:
- NC not ready.
- The NC switches to follow-up mode.
- Channel not ready.
- NC Start disable in this channel.
- Interface signals are set.
- Alarm display.
- NC Stop on alarm.
Remedy:
Perform the following checks:
1) Using the configuration display or the associated machine data, check whether the
number and type (1-axis or 2-axis) of the modules match your bus setup.
2) Check whether the red LED is illuminated on the displayed drive module. If this is not
the case, then usually the module does not have any power.
© Siemens AG, 2005. All rights reserved
SINUMERIK 840D sl/840D/840Di/810D Diagnostics Guide (DA), 08/2005 Edition
Overview of Alarms
2-819