08/2005
Remedy:
- check that the sensor is connected correctly.
- check the parameterization (p0600, p0601).
- induction motors: Deactivate temperature sensor fault (p0607 = 0).
See also: p0600, p0601, p0607
207080
<location>Drive: Open-loop/closed-loop control parameterization error
Reaction:
NONE
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
Closed-loop control parameters have been parameterized incorrectly (e.g. p0356 =
L_spread = 0).
Fault value (r0949, decimal):
The fault value includes the parameter number involved.
The following parameter numbers only occur as fault values for vector drives:
p0310, for synchronous motors: p0341, p0344, p0350, p0357
The following parameter numbers do not occur as fault values for synchronous motors:
p0354, p0358, p0360
See also: p0310, p0311, p0341, p0344, p0350, p0354, p0356, p0358, p0360, p0400,
p0640, p1082, p1300
Remedy:
Modify the parameter indicated in the fault value (r0949) (e.g. p0640 = current limit > 0).
See also: p0311, p0341, p0344, p0350, p0354, p0356, p0358, p0360, p0400, p0640,
p1082
207082
<location>Macro: Execution not possible
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The macro cannot be executed.
Fault value (r0949, hexadecimal):
The fault code is in byte 1, possibly supplementary information is in byte 2 and the high
word contains the parameter number involved if this is available.
Fault codes:
Fault for the trigger parameter itself:
-20 called file is not valid for parameter 15
-21 called file is not valid for parameter 700
-22 called file is not valid for parameter 1000
-23 called file is not valid for parameter 1500
-24 data type of a TAG is incorrect (e.g.: Index, number or bit is not U16)
Faults for the parameters to be set:
-25 error level has an undefined value
-26 mode has an undefined value
-27 a value was entered as string in the tag value that is not "DEFAULT"
-31 entered DO type unknown
-32 a device was not able to be found for the determined DO number
-34 a trigger parameter was recursively called
-35 it is not permissible to write to the parameter via macro
-36 check, writing to a parameter unsuccessful, parameter can only be read, not available,
incorrect data type, value range or assignment incorrect
-37 source parameter for a BICO connection was not able to be determined
-38 an index was set for a non-indexed parameter
-39 no index was set for an indexed parameter
-41 a bit operation is only permissible for parameters with the parameter format
DISPLAY_BIN
-42 a value not equal to 0 or 1 was set for a bit operation
-43 reading the parameter to be changed by the bit operation was unsuccessful
-51 factory setting for DEVICE may only be executed on the DEVICE
-61 the setting of a value was unsuccessful
© Siemens AG, 2005. All rights reserved
SINUMERIK 840D sl/840D/840Di/810D Diagnostics Guide (DA), 08/2005 Edition
Overview of Alarms
2-687