08/2005
Cause:
A message buffer overflow.
Alarm value (r2124, decimal):
1: Non-cyclic send buffer (SDO response buffer) overflow.
2: Non-cyclic receive buffer (SDO receive buffer) overflow.
3: Cyclic send buffer (PDO send buffer) overflow.
Remedy:
Check the bus cable.
Set a higher baud rate (p8622).
Check the bit timing and if required optimize (p8623).
Re alarm value = 2:
- reduce the cycle times of the SDO receive messages.
208754
<location>CBC: Incorrect communications mode
Reaction:
NONE
Acknowledge:
NONE
Cause:
In the "operational" mode, an attempt was made to change parameters p8700 ... p8737.
Remedy:
Change into the "pre-operational" or "stopped" mode.
208755
<location>CBC: Obj cannot be mapped
Reaction:
NONE
Acknowledge:
NONE
Cause:
The CANopen object is not provided for the Process Data Object (PDO) Mapping.
Remedy:
Use a CANopen object intended for the PDO mapping or enter 0.
The following objects can be mapped in the Receive Process Data Object (RPDO) or
Transmit Process Data Object (TPDO):
- RPDO: 6040 hex, 6060 hex, 60FF hex, 6071 hex.
- TPDO: 6041 hex, 6061 hex, 6063 hex, 6069 hex, 606B hex, 606C hex, 6074 hex.
Note:
As long as A08755 is present, the COB-ID cannot be set to valid.
208756
<location>CBC: Number of mapped bytes exceeded
Reaction:
NONE
Acknowledge:
NONE
Cause:
The number of bytes of the mapped objects exceeds the telegram size for net data. A
maximum of 8 bytes is permissible.
Remedy:
Map fewer objects or objects with a smaller data type.
See also: p8710, p8711, p8712, p8713, p8714, p8715, p8716, p8717, p8730, p8731,
p8732, p8733, p8734, p8735, p8736, p8737
208757
<location>CBC: Set COB-ID invalid
Reaction:
NONE
Acknowledge:
NONE
Cause:
For online operation, the appropriate COB-ID must be set invalid before mapping.
Example:
Mapping for RPDO 1 should be changed (p8710[0]).
--> set p8700[0] = C00006E0 hex (invalid COB-ID)
--> set p8710[0] as required.
--> p8700[0] enter a valid COB-ID
Remedy:
Set the COB-ID to invalid.
208758
<location>CBC: Number of PDO channels too low
Reaction:
NONE
Acknowledge:
NONE
Cause:
The number of PDO channels in p8740 has either been set to 0 or too low.
© Siemens AG, 2005. All rights reserved
SINUMERIK 840D sl/840D/840Di/810D Diagnostics Guide (DA), 08/2005 Edition
Overview of Alarms
2-715