08/2005
201512
<location>BICO: No normalization available
Reaction:
A_INFEED: OFF2 (OFF1)
SERVO: OFF2
Acknowledge:
POWER ON
Cause:
An attempt was made to determine a conversion factor for a normalization that does not
exist.
Fault value (r0949, decimal):
Unit (e.g. corresponding to SPEED) for which an attempt was made to determine a factor.
Remedy:
Apply normalization or check the transfer value.
201513
<location>BICO: Spanning DO between different normalizations
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The requested interconnection was set up. However, a conversion is made between the
BICO output and BICO input using the reference values.
An interconnection is made between different drive objects and the BICO output has
different normalized units than the BICO input or the normalized units are the same but the
reference values are different.
Example:
The BICO output has, as standard unit, voltage and the BICO input has current; both lie in
different drive objects.
This means that the factor p2002 (contains the reference value for current) / p2001
(contains the reference value for voltage) is calculated between the BICO output and BICO
input.
Fault value (r0949, decimal):
Parameter number of the BICO input (signal receiver).
Remedy:
No correction needed.
201514
<location>BICO: Error when writing during a reconnect
Reaction:
NONE
Acknowledge:
NONE
Cause:
During a reconnect operation (e.g. at run-up or download - but cannot occur in normal
operation) a parameter was not able to be written into.
Example:
When writing to a double word BICO input in the second index, the memory areas overlap
(e.g. p8861). The parameter is then reset to the factory setting.
Alarm value (r2124, decimal):
Parameter number of the BICO input (signal receiver).
Remedy:
None necessary.
201590
<location>Drive: Motor maintenance interval expired
Reaction:
NONE
Acknowledge:
NONE
Cause:
The selected service/maintenance interval for this motor was reached.
Fault value (r0949, decimal):
Motor data set number.
See also: p0650, p0651
Remedy:
Carry-out service/maintenance and reset the service/maintenance interval (p0651).
201600
<location>SI CU: STOP A initiated
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (POWER ON)
© Siemens AG, 2005. All rights reserved
SINUMERIK 840D sl/840D/840Di/810D Diagnostics Guide (DA), 08/2005 Edition
Overview of Alarms
2-649