08/2005
Cause:
An invalid data type was detected when evaluating parameter files PSxxxyyy.ACX,
PTxxxyyy.ACX, CAxxxyyy.ACX or CCxxxyyy.ACX, saved on the CompactFlash Card.
Alarm value (r2124, hexadecimal):
Only for internal Siemens troubleshooting.
Remedy:
Restore the factory setting using (p0976 = 1) and re-load the project into the drive unit.
Operation without any restrictions is then possible.
After downloading the project, save the parameterization in STARTER using the function
"Copy RAM to ROM" or with p0977 = 1. This means that the incorrect parameter files are
overwritten on the CompactFlash Card.
201046
<location>CU CompactFlash: Configuration data invalid
Reaction:
NONE
Acknowledge:
NONE
Cause:
An invalid data type was detected when evaluating the parameter files PSxxxyyy.ACX,
PTxxxyyy.ACX, CAxxxyyy.ACX or CCxxxyyy.ACX saved on the CompactFlash Card.
Alarm value (r2124, hexadecimal):
Only for internal Siemens troubleshooting.
Remedy:
Restore the factory setting using (p0976 = 1) and re-load the project into the drive unit.
Operation without any restrictions is then possible.
After downloading the project, save the parameterization in STARTER using the function
"Copy RAM to ROM" or with p0977 = 1 so that the incorrect parameter files are overwritten
on the CompactFlash Card.
201047
<location>ACX: Parameter write error
Reaction:
NONE
Acknowledge:
NONE
Cause:
When evaluating the parameters files PSxxxyyy.ACX, PTxxxyyy.ACX, CAxxxyyy.ACX or
CCxxxyyy.ACX, saved on the CompactFlash Card, a parameter value was not able to be
transferred into the control unit memory.
Alarm value (r2124, hexadecimal):
Only for internal Siemens troubleshooting.
Remedy:
Restore the factory setting using (p0976 = 1) and re-load the project into the drive unit.
Operation without any restrictions is then possible.
After downloading the project, save the parameterization in STARTER using the function
"Copy RAM to ROM" or with p0977 = 1. This means that the incorrect parameter files are
overwritten on the CompactFlash Card.
201049
<location>CU CompactFlash: It is not possible write into the file
Reaction:
NONE
Acknowledge:
NONE
Cause:
It is not possible to write into a write-protective file (PSxxxxxx.acx). The write request was
interrupted.
Alarm value (r2124, decimal):
Drive object number.
Remedy:
Check whether the write-protected attribute has been set for the files on the CompactFlash
Card under .../USER/SINAMICS/DATA/... When required, remove write protection and
save again (e.g. set p0971 to 1).
201050
<location>CompactFlash card and device not compatible
Reaction:
A_INFEED: OFF2 (NONE, OFF1)
SERVO: OFF2 (NONE, OFF1, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
The CompactFlash Card and the device type do not match (e.g. a CompactFlash Card for
SINAMICS S is inserted in SINAMICS G).
Remedy:
- insert the matching CompactFlash Card
- use the matching control unit or power module.
© Siemens AG, 2005. All rights reserved
SINUMERIK 840D sl/840D/840Di/810D Diagnostics Guide (DA), 08/2005 Edition
Overview of Alarms
2-627